CBHK/CBVK

The CBHK/CBVK has been designed with increased insulation meeting the demands for 1000VAC/1440VDC. 

The resistor elements are wire wound on mica support sheets. The outer housing is an aluminium profile isolated with micanite sheets on all inner surfaces. The resistor elements are fixed symmetrical in the profile by ceramic insulators. This ensures a symmetric expansion of the resistors and a maximum stability at high load impulses.

The aluminium profile with the fixed resistor element is filled with quarts sand. This ensures a minimum change of the resistor surface temperature even if the resistor element reaches its maximum temperature during a pulse load.

The standard cables are 300 mm AWG 18-10 PTFE, neutral color for 1000V. 

Danotherm has developed Thermal Simulation corresponding to all resistor types and resistor values. By using these models we are able to calculate the temperature rises in the resistor wire and on the surface for all possible load applications. We offer our assistance to our customers to find the optimum solution for any situation. The resistors can be delivered with internal or external thermostats.

 

CBHK/CBVK Datasheet

 

Specifications

Power Range 110W - 330W
Pulse Load 40s/120s:. . . . . . . . . . . . . . . . . . . . . . . . . . . 330W - 1000W 10s/120s:. . . . . . . . . . . . . . . . . . . . . . . . . . .1000W - 4.5kW 5s/120s: . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.8kW - 8.3kW 1s/120s: . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5.5kW - 25kW
Over Load 10 x in 10s / 120s; 60 x in 1s / 120s
De-rating Linear: 40°C = PN to 90°C = 0.75*PN
Environmental -40 °C – 90 °C
Resistance Tolerance ± 10% (standard) or ± 5% (optional)
Dielectric Strength 3500VAC 1 minute
Working Voltage UL: 1000VAC; 1400V DC / CE: 1000VAC; 1400VDC
Insulation Resistance > 20 M OHM
Protection class IP50
Thermo watch (optional) 130°C - 200°C
Approvals UL 508
 
 
 